Please note that UNLV may not own the copyright to these materials and cannot provide permission to publish or distribute materials when UNLV is not the copyright holder. The user is solely responsible for determining the copyright status of materials and obtaining permission to use material from the copyright holder and for determining whether any permissions relating to any other rights are necessary for the intended use, and for obtaining all required permissions beyond that allowed by fair use.
Read more about our reproduction and use policy.
I agree.M 57-2Z LVEGAS 13 444P . FS LA OL J7 ORIG FS LA OL JPM LA OL . S»63 THE TWO BOOSTER PUMPS HAVE BEEN RUN EVERY NIGHT* MADE TEST TODAY, WITHOUT PUMPS 24 POUNDS, WITH PUMPS 32 POUNDS, AT 16 INCH METERS. FLOW A? METERS 2250 AND 455© GALS PER MIN AT 2PM WITH 11 POUNDS ON GAUGE AT PUMPS*, ALL WELLS ON BUT NO-2 AND NO-8, 5 FT 6 INCHES WATER Jfi RESERVOIR. CAPY OF PUMPS 3000 GALS EACH AT 40 FT HEAD, BUT WE HAVE ONLY 21 FT HEAD AT DISCHARGE AT PUMPS* WILL YOU TALK TO BYRON JACKSON CO TO SEE IF YOU CAN CHANGE RUNNERS OF PUMPS TO DEVELOP MORE WATER AT A40 FT HEAD M-72 JMA.